Output Frequency 2-125
against insulation breakdown resulting from high dv/dt. When using motor
line reactors, it is recommended that the drive PWM frequency be set to its
lowest value to minimize losses in the reactors.
By using an output reactor the effective motor voltage will be lower because
of the voltage drop across the reactor - this may also mean a reduction of
motor torque.
Output Frequency [Output Frequency]
This parameter displays the actual output frequency of the drive. The output
frequency is created by a summation of commanded frequency and any
active speed regulator such as slip compensation, PI Loop, bus regulator.
The actual output may be different than the commanded frequency.
Output Power This parameter displays the output kW of the drive. The output power is a
calculated value and tends to be inaccurate at lower speeds. It is not
recommended for use as a process variable to control a process.
Output Voltage [Output Voltage]
This parameter displays the actual output voltage at the drive output
terminals. The actual output voltage may be different than that determined
by the sensorless vector or V/Hz algorithms because it may be modified by
features such as the Auto-Economizer.

Table of Contents

Other manuals for Allen-Bradley PowerFlex 70

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 70 and is the answer not in the manual?

Allen-Bradley PowerFlex 70 Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 70
CategoryController
LanguageEnglish

Related product manuals