Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017 125
Appendix B
Specifications
This appendix presents the specifications for the adapter.
Communication
Regulatory Compliance
Network
Protocol
Data Rates
EtherNet/IP network
10 Mbps full-duplex, 10 Mbps half-duplex, 100 Mbps full-duplex, or 100
Mbps half-duplex
Connection Limits 30 TCP connections
16 simultaneous CIP-based network explicit connections plus one exclusive
owner I/O connection.
Class 1 I/O connections (for example, from a ControlLogix® controller)
uses an exclusive-owner I/O connection.
Explicit Messaging when ‘connected’ is chosen (for example, in a checkbox in
RSLogix 5000® software) uses a CIP-based network explicit connection.
Explicit Messaging where the ‘connected’ option is not chosen, does not use
a CIP-based network explicit connection.
Requested Packet Interval (RPI) 2 ms minimum
Packet Rate At least 1000 total packets per second (500 in and 500 out)
UL UL508C
cUL CAN / CSA C22.2 No. 14-M91
CE EN50178 and EN61800-3
CTick EN61800-3
IMPORTANT This product is a category C2 product according to IEC 61800-3. In a domestic
environment, this product causes radio interference, in which case
supplementary mitigation measures can be required.