Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017 159
EtherNet/IP Objects Appendix D
DPI Time Object
Table 72 - DPI Diagnostic Object: Instance Attributes
Attribute ID Access Rule Name Data Type Description
0 Get Full/All Information STRUCT of:
BOOL[32]
CONTAINER
(1)
CONTAINER
CONTAINER
CONTAINER
UINT
UINT
STRING[4]
UINT
UINT
UINT
INT
UDINT
STRING[16]
Descriptor (see page 150
)
Value
Minimum value
Maximum value
Default value
Pad Word
Pad Word
Units (for example, Amps, Hz)
Multiplier
(2)
Divisor
(2)
Base
(2)
Offset
(2)
Link (source of the value) (0 = no link)
Diagnostic name text
1 Get/Set Value Various Diagnostic item value
2 Get International Diagnostic
Item Text
Struct of:
STRINGN
STRINGN
Diagnostic name text
Diagnostic units text
3 Get International Full Read All STRUCT of:
BOOL[32]
CONTAINER
CONTAINER
CONTAINER
CONTAINER
UINT
UINT
UINT
UINT
UINT
INT
UDINT
BOOL[32]
STRINGN
STRINGN
Descriptor
Value
Minimum
Maximum
Default
Pad word
Pad word
Multiplier
Divisor
Base
Offset
Pad
Extended descriptor
Diagnostic name text
Diagnostic units text
(1) A CONTAINER is a 32-bit block of data that contains the data type used by a value. If signed, the value is sign that is extended. Padding is
used in the CONTAINER to make sure that it is always 32-bits.
(2) This value is used in the formulas that are used to convert the value between display units and internal units. See Formulas for Converting on
page 152.
Table 73 - DPI Time Object: Class Code
Hexadecimal Decimal
0 x9B 155