128 Rockwell Automation Publication 750COM-UM009A-EN-P - May 2017
Appendix C Interface Parameters
Parameter List
Icon Descriptions
This icon indicates that the parameter value cannot be changed until the drive is stopped.
This icon indicates that the parameter cannot be set to DataLink In.
This icon indicates that an explicit message write cannot change the parameter value. The parameter value can be changed by using a datalink.
Table 25 - Port 0: Parameter List
No. Display Name
Extended Name
Description
Values
Read-Write
Data Type
Parameter 30
[Access Level]
300 Net Addr Sel
Network Address Selection
Selects the source for the interface node address, subnet mask, and gateway address
when the rotary switches on the main control board are set to 999.
‘Parameters’ (1) – The address comes from parameters 302
[IP Addr Cfg 1]…313
[Gateway Cfg 4].
‘BOOTP’ (2) – The address comes from a BOOTP server on the network.
‘DHCP’ (3) – The address comes from a DHCP server on the network, this could be a
Stratix® switch.
A power cycle or reset is needed for changes to this parameter to take effect.
Default:
Options:
3 = ‘DHCP’
1 = ‘Parameters’
2 = ‘BOOTP’
3 = ‘DHCP’
RW 32-bit
Integer
0
301 Net Addr Src
Network Address Source
Displays the active source for the interface node address, subnet mask, and gateway
address.
‘Switches’ (0) – The address comes from the rotary switches on the main control board.
‘Parameters’ (1) – The address comes from parameters 302
[IP Addr Cfg 1]…313
[Gateway Cfg 4].
‘BOOTP’ (2) – The address comes from a BOOTP server on the network.
‘DHCP’ (3) – The address comes from a DHCP server on the network, this could be a
Stratix switch.
Default:
Options:
0 = ‘Switches’
0 = ‘Switches’
1 = ‘Parameters’
2 = ‘BOOTP’
3 = ‘DHCP’
RO 32-bit
Integer
0
302
303
304
305
IP Addr Cfg 1
IP Addr Cfg 2
IP Addr Cfg 3
IP Addr Cfg 4
IP Address Configuration n
Sets the first, second, third, and fourth byte in the IP address when parameter 301
[Net
Addr Src] is set to 1 ‘Parameters’.
A power cycle or reset is needed for changes to this parameter to take effect.
Default:
Min/Max:
0
0/255
RW 32-bit
Integer
0
306
307
308
309
Subnet Cfg 1
Subnet Cfg 2
Subnet Cfg 3
Subnet Cfg 4
Subnet Configuration n
Sets the first, second, third, and fourth byte in the subnet mask when parameter 301
[Net Addr Src] is set to 1 ‘Parameters’. The subnet mask cannot be 0.0.0.0.
A power cycle or reset is needed for changes to this parameter to take effect.
Default:
Min/Max:
0
0/255
RW 32-bit
Integer
0