EasyManuals Logo
Home>Ansul>Security System>AUTOPULSE Z-20

Ansul AUTOPULSE Z-20 User Manual

Ansul AUTOPULSE Z-20
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #26 background imageLoading...
Page #26 background image
5.2.3 Wiring parameters
Table 14 identifies the IDNet wiring parameters that you must consider when installing this card. For additional wiring information, see
Addressable Fire Alarm Panels Field Wiring Specifications (900-408).
Table 14: IDNet wiring parameters
IDNet wiring capacitance parameters
Parameter Value
Maximum supported channel capacitance The sum of line-to-line capacitance, plus the capacitance of either
line-to-shield (if shield is present) = 0.6 µF
IDNet wiring Class A, Class B and Class X limits
Channel loading Up to 125 devices 126 to 250 devices
Max. resistance to compatible devices. (Include the
2081-9044 Overvoltage Protector resistance when
applicable)
50 ohms maximum 35 ohms maximum
Maximum wiring distance*:
(18 AWG, 16 AWG, 14 AWG, 12 AWG)
4000 ft (1219 m) 2500 ft (762 m)
Note:
The maximum wiring distance is the maximum distance from both the IDNet control terminals (primary and return) to the farthest
device on the circuit. See Figure 18.
The maximum wiring distance is determined by either reaching the maximum resistance, the maximum capacitance, or the stated
maximum distance, whichever occurs first.
The total circuit cable load (amount of cable used) must not exceed 12,500 ft (3,8 km).
Twisted wiring is recommended for improved noise immunity.
Figure 18: Maximum wiring distance
Table 15: IDNet wiring considerations
External wiring must be shielded (for lightning suppression) and 2081-9044 Overvoltage Protectors
must be installed at building exit and entrance locations.
For more information, refer to the Model 2081-9044 Overvoltage Protector Installation Instructions
(579-832).
Capacitance; each protector adds 0.006 µF across the connected line.
Resistance; each protector adds 3 ohms per line of series resistance; both IDNet wires are
protected; 6 ohms per protector will be added to the total loop resistance.
The maximum distance of a single protected wiring run is 3270 ft (1 km).
IDNet wiring considerations
using 2081-9044 Overvoltage
Protectors
(2081-9044 is UL listed to Standard
1459, Standard for Telephone
Equipment)
See the 2081-9044 Overvoltage Protector Installation Instructions (574-832) for additional information.
page 24 579-1102AR Rev C
Z-20 Agent Releasing Panel Installation Manual

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ansul AUTOPULSE Z-20 and is the answer not in the manual?

Ansul AUTOPULSE Z-20 Specifications

General IconGeneral
BrandAnsul
ModelAUTOPULSE Z-20
CategorySecurity System
LanguageEnglish

Related product manuals