6 Optional modules and cards
The AUTOPULSE Z-20 can be ordered with a variety of optional cards and modules, depending on the system requirements.
8 Point Zone/ Relay Card
The 8-point zone/relay Card (4007-9801) mounts in the AUTOPULSE Z-20 panel. Up to four cards can be added. Each card monitors up to
eight Class B or four Class A zones, or eight relay contacts. For more information about the 8-point zone/relay card, see the 4007-9801 8-
Point Zone/Relay Card installation instructions (579-1103).
25 V Regulator Module
The 25 V regulator module (4007-9802) regulates the panel power supply output received from the NAC power supply to a 25 V DC level.
The 25 V DC regulated output is isolated from the panel and complies with power-limited requirements. For more information about the
25 V regulator module, see the 25 V Regulator Module installation instructions (579-812).
IDNet+ Loop Expansion Card
The IDNet+ loop expansion card (4007-9803) mounts directly on the NAC power supply. Up to two cards can be added. Each card adds a
single Class A/Class B IDNet+ loop and increases the device capacity by 75 points. For more information about the IDNet+ loop expansion
card, see the 4007-9803 IDNet+ Loop Expansion Card installation instructions (579-1106).
LED module
The operator uses the LED module (4007-9805) to view the simultaneous signaling of alarm and trouble conditions on up to 24 zones. All
the LEDs have configurable colors, red or yellow, except the LEDs in the last column, which are configurable as red or green.
For more information about the LED module, see the 4007-9805 LED Module installation instructions (579-1105).
The SDACT card
The SDACT card (4007-9806) can be mounted in the AUTOPULSE Z-20 panel. It is used to notify a central station when an event occurs, to
report changes to a specific point, and to connect a transmitter to a central station. For more information, refer to the 579-954 manual.
The SDACT card only meets the requirements of UL 864 9th edition.
Alarm Relay Card
The Alarm relay card (4007-9809) is used to provide common unsupervised control functions or indications for devices. Each relay module
has three circuits (alarm, trouble, and supervisory signals). For more information about alarm relay card, see the City and Relay Cards
installation instructions (579-955).
page 32 579-1102AR Rev C
Z-20 Agent Releasing Panel Installation Manual