Mounting Instructions
asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4,
116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS
Page 22
6.3 Mounting the Operator Panel BS-430
Instructions
Remarks
Illustrations
Unlock the front panel
by turning the unbraco
key clockwise.
Open the front panel.
In order to easily
access the
mounting holes
when mounting
the cabinet, the
front panel should
be removed.
Unscrew and disconnect
the earth cable from the
termination point inside
the cabinet.
Note: Do NOT
unscrew the earth
cable from the
connection point
on the front panel
(PE=Protective
Earth).
Unscrew the 4 wing nuts
located on the right and
left hand side of the
cabinet, then close the
front panel, and remove
the front panel from the
cabinet.
Mark and drill the 3
holes.
The cabinet has 5
mounting holes
located at the
rear. The 3 upper
holes are of key-
hole-type.
Partly fasten the upper
screws.
Hang the cabinet onto
the upper screws.
Partly fasten the bottom
screw.
Tighten all screws.
Feed all the external
cables into the cabinet
from the top through the
suitable cable inlets.
For detailed
information on the
connection of
external cables,
see chapter 10.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica AutroSafe and is the answer not in the manual?

Autronica AutroSafe Specifications

General IconGeneral
BrandAutronica
ModelAutroSafe
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals