Connecting External Cables
asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4,
116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS
Page 41
10.5.2 Connections to Connector J2, Power Board BSF-400
10.5.3 Example of the Interconnection of Several Power Cabinets
The example below shows the interconnection of two Power Cabinets
(with BPS-410) on the AutroFieldBus. Note that the AutroFieldBus
always goes from AFB A on the main terminal block inside BS-420/BC-
420 to AFB B on the J2 connector on the Power Board BSF-400, then
from AFB A to the next unit. The cable finally returns to AFB B on the
main terminal block.