Connecting External Cables
asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4,
116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS
Page 45
10.6.4 Connection to Controller Board BSA-400
The BSA-400 board on all panels provides two separate 10/100Mbit
Ethernet ports. The connector is an RJ-45 modular jack, suitable for
shielded cable CAT5 which allows cable lengths up to 100m.
LED 1
Activity LED
LED 2
If ON, 100MBit/s, if OFF, 10MBit/s
10.6.5 Common Earth Connections
All panels must be connected to a common earth for EMC compliance.
2 x 2
24V
Fire Alarm
Control Panel
BS-420
Controller
BC-420 / BC-440
Power
BPS-410
BU-BV-420
BU-BV-420
Operator
Panel
BS-430
2 x 2
24V
Shielded or armoured cable must be used for the 24V DC power
supply.
Note:
For information on common earth connections for Power Cabinet STX
Range, refer to documentation listed in chapter 6.6.