Appendix B Power
asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4,
116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS
Page 82
16.11 Connector Description BPS-410
Connector
Description
BPS-410
J25
Power Supply
To BSP-405 (Mean Well Power Supply)
J20
Battery
connector
To Battery 27,3VDC charging
J17
Temp.
sensor/Mean
Well Control
Not applicable. Applies to BPS-405 (obsolete).
J26 1-3
Powernet
control
Control wires for power supply.
J26 4-6
Fault Relay
Fault Relay (NO, NC, com) Fault output.
J19
Output A1
24V/2A (BSA-400 V
in
1 +/0V)
J18
Output A2
24V/2A (BSA-400 V
in
2 +/0V)
J24
Output B1
24V/2A, general power output
J23
Output B2
24V/2A, general power output
J22
Output C1
24V/2A with interrupt at init
J21
Output C2
24V/2A with interrupt at init
The power outputs have different properties. They can all deliver 2A
each (limited by total power available).
Output
Description
Output A
These will always be ON. Will be turned OFF by a
short- circuit only.
Output B
These are initially ON, but may be switched OFF/ON
from AutroSafe.
Output C
These will be turned OFF during start-up of BSF-400
(initialization). May be switched OFF/ON from
AutroSafe. Power to I/O modules.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autronica AutroSafe and is the answer not in the manual?

Autronica AutroSafe Specifications

General IconGeneral
BrandAutronica
ModelAutroSafe
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals