Service and Maintenance
asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4,
116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS
Page 62
Check the fault warning function from detector zones by removing a detector in each zone.
Activate a fault (remove battery fuse) and observe:
- the Fault indicator starts to blink
- a fault warning is displayed
- the internal buzzer is turned ON
- the Fault Warning Routing Equipment (FWRE) output is activated (if any)
Verify all conditions, i.e.:
- Fire Alarm condition
- Fire Warning condition
- Fault Warning condition
- Disablement condition
- Test condition
On completion of checks, ensure that only the green "Power" indicator is ON when the panel
is in its idle state (normal operation).
• Take necessary precautions to avoid short-circuiting 24V
circuits while performing service and maintenance. Make sure
to remove the output’s fuse.
• If a fuse is broken, replace the broken fuse with one that is
exactly the same.
• Refer to circuit board layout for information on the location of
fuses.
14.5 Battery Replacement and Maintenance
A capacity test of the battery should be carried out annually.
Local/national requirements apply.
We strongly recommend that batteries are replaced every 4 years, the
first time after 4 years (refer to manufacture date indicated on the
battery).
If a fault arises on the panel that cannot be rectified, contact your
nearest Autronica Fire and Security office for qualified assistance.
14.6 Testing
To ensure that the system works properly during normal operation after
commissioning, the whole system (control panel, detectors, control
functions, activation groups, activation of inputs/outputs) should be
verified.