Mounting Instructions
asafeinstall_dgb, AutroSafe Interactive Fire Detection System, Release 4,
116-P-ASAFE-INSTALL/DGB, Doc-1004796-2, 2021-08-23, Autronica Fire and Security AS
Page 27
6.7 Mounting Power Supply Unit BPS-410
The unit can be mounted inside a rack or consol. The hole and screw
dimensions are shown below.
Note that the BPS-410 Power Supply Unit 24VDC/10A is delivered as
two separate part numbers:
116-BPS-410 for 230VAC
116-BPS-410/115 for 115VAC
The dipswitch settings on the Power Board BSF-400 (dipswitch S6-6)
determines the type of power unit.
Dip-switch
Name
Description
S6-6
Power Unit Type
OFF: BPS-410
ON: BPS-405 (obsolete)
ip-switch Name Description
For further information on dipswitch settings, refer to 16.10. Note that
when using Power Unit BPS-410 (including a 24V/10A power supply), a
calibration procedure must be performed. Refer to the Commissioning
Handbook, Calibration Procedure Power Unit BPS-410.