Space for
The control valve is designed to withstand severe operating conditions. However, in order to
achieve its optimal performance, install the valve to a location with the following conditions:
Ambient temperature: -30 to +70 °C
Relative humidity: 10 to 90 %
Vibration: 2 G max. (5 to 400 Hz)
Handling Precautions
The vibration specification is for the AVP positioner mounted on the PSA actuator.
CAUTION
If the KZ03 pressure regulator with air filter is mounted on this device,
install this device on the piping so that the drain of the KZ03 faces down-
ward. If the KZ03 cannot be vertical (if its drain does not face downward),
remove it from this device.
Rainwater may enter the pressure gauge, so install this device so that the
gauge does not face upward or downward. Also, there is a rainwater drain
hole at the bottom of the pressure gauge. The hole must be positioned
facing downward.