64
3.2 — 06E Series Compressors - Physical Data (Page 1 of 2)
(a) Approximate condensing temperature ranges. CHECK ACTUAL PERFORMANCE DATA FOR ANY NEW APPLICATION ESPECIALLY AT OR
NEAR UPPER OR LOWER LIMIT: Low Temperature=70 to 120 Deg.F. (21 to 49 C), Medium Temperature=80 to 130 F (27 to 54 C) and High Tem-
perature (R-407A, C, F only) = 80 to 150 F (27 to 64 C).
(d) The models shown are new oil-less models. Models with oil had a 0, 1, or 2 in the 5th digit of the model number.
(e) The 06ER166 and 06EM266 models are no longer built new, but service replacements are built and available. For new applications, the 06ER166
and 06EM266 models have been replaced by the 06ER465 and 06EA565.
CARRIER/
CARLYLE MODEL
NUMBER (d)
STANDARD
SERVICE
REPLACEMENT
MODEL
SUCTION TEMPERATURE RANGE ...(a)
R-404A/507, R-448A and
R-449A
R-134a R-407A, R-407C and R-407F
Deg. F Deg. C Deg. F Deg. C Deg. F Deg. C
06ER450... 06EY450... -40 to 0 -40 to -18 -10 to 55 -23 to 13 -35 to 0 -37 to -18
06EM450... 06EZ450... 0 to 25 -18 to -4 -10 to 55 -23 to 13 0 to 45 -18 to 7
06EA550... 06ET250... 0 to 50 -18 to 10 — — 0 to 55 -18 to 13
06ER166... (e) 06EY466... -40 to 0 -40 to 18 -10 to 55 -23 to 13 -35 to 0 -37 to -18
06EM266... (e) 06EZ266... 0 to 45 -18 to 7 -10 to 55 -23 to 13 0 to 50 -18 to 10
06ER465... 06EY465... -40 to 0 -40 to -18 -10 to 55 -23 to 13 -35 to 0 -37 to -18
06EA565... 06ET265... 0 to 50 -18 to 10 -10 to 55 -23 to 13 0 to 50 -18 to 13
06ER475... 06EY475... -40 to 0 -40 to -18 -10 to 55 -23 to 13 -35 to 0 -37 to -18
06EM475... 06EZ475... 0 to 40 -18 to 4 -10 to 55 -23 to 13 0 to 45 -18 to 7
06EA575... 06ET275... 0 to 50 -18 to 10 — — 0 to 55 -18 to 13
06ER399... 06EY399... -40 to 0 -40 to -18 -10 to 55 -23 to 13 -35 to 0 -37 to -18
06EM499... 06EZ499... 0 to 40 -18 to 4 -10 to 55 -23 to 13 0 to 45 -18 to 7
06EA599... 06ET299... 0 to 50 -18 to 10 — — 0 to 55 -18 to 13