66
3.3 — 06CC Series Compressors - Physical Data (Page 1 of 2)
(f) Approximate condensing temperature ranges. CHECK ACTUAL PERFORMANCE DATA FOR ANY NEW APPLICATION,
ESPECIALLY AT OR NEAR UPPER OR LOWER LIMIT: Low Temperature = 70 to 130 F (21 to 55 C).
(g) To provide a 6-cylinder body needed for Compound Cooling, the normal 4-cylinder model 16, 18 and
50 Cfm compressors are built using the 24, 18, and 65 Cfm 6-cylinder bodies respectively. The
actual Cfm reduction is achieved by modifying the running gear.
(h) R404A/R-507 CANNOT be used in the small “D” body size Compound Cooling compressors (16 to 37 Cfm), manufactured prior
to Serial No. 2099J.
(i) R-134a CANNOT be used in any Compound Cooling compressor.
CARRIER/
CARLYLE MODEL
NUMBER
STANDARD
SERVICE
REPLACEMENT
MODEL
SUCTION TEMPERATURE RANGE ...(f)
R-404A/507, R448-A and
R-449A
R-134a R-407A, R-407C and R-407F
Deg. F (h) Deg. C (h) Deg. F Deg. C Deg. F Deg. C
06CC016... (g) 06CY016... -40 to -10 -40 to -23 (i) (i) -40 to -10 -40 to -23
06CC017... 06CY017... -40 to -10 -40 to -23 (i) (i) -40 to -10 -40 to -23
06CC018... (g) 06CY018... -40 to -10 -40 to -23 (i) (i) -40 to -10 -40 to -23
06CC124... 06CY124... -60 to -10 -51 to -23 (i) (i) -40 to -10 -40 to -23
06CC125... 06CY125... -60 to -10 -51 to -23 (i) (i) -40 to -10 -40 to -23
06CC228... 06CY228... -60 to -10 -51 to -23 (i) (i) -40 to -10 -40 to -23
06CC337... 06CY337... -60 to -10 -51 to -23 (i) (i) -40 to -10 -40 to -23
06CC550... (g) 06CY550... -40 to -10 -40 to -23 (i) (i) -40 to -10 -40 to -23
06CC665... 06CY665... -60 to -10 -51 to -23 (i) (i) -40 to -10 -40 to -23
06CC675... 06CY675... -60 to -10 -51 to -23 (i) (i) -40 to -10 -40 to -23
06CC899... 06CY899... -60 to -10 -51 to -23 (i) (i) -40 to -10 -40 to -23