30

The power supply must conform to the specication on the chiller
nameplate. The supply voltage must be within the range specied
in the electrical data table. For connections refer to the wiring
diagrams.
WARNING: Operation of the chiller with an improper supply
voltage or excessive phase imbalance constitutes abuse which
will invalidate the Carrier warranty. If the phase imbalance
exceeds 2% for voltage, or 10% for current, contact your local
electricity supply at once and ensure that the chiller is not
switched on until corrective measures have been taken.

100 x max. deviation from average voltage
Average voltage
Example:
On a 400 V - 3 ph - 50 Hz supply, the individual phase voltages
were measured to be:
AB = 406 V; BC = 399 V; AC = 394 V
Average voltage = (406 + 399 + 394)/3 = 1199/3
= 399.7 say 400 V
Calculate the maximum deviation from the 400 V average:
(AB) = 406 - 400 = 6
(BC) = 400 - 399 = 1
(CA) = 400 - 394 = 6
The maximum deviation from the average is 6 V. The greatest
percentage deviation is:
100 x 6/400 = 1.5%
This is less than the permissible 2% and is therefore acceptable.
Motor

• 30HXC080-190unitshaveasinglepowerconnectionpoint;30HXC200-375
unitshavetwoconnectionpoints.
• Thecontrolboxincludesthefollowingstandardfeatures:
- Starter and motor protection devices for each compressor
- Control devices

Allconnectionstothesystemandtheelectricalinstallationsmustbeinfull
accordancewithallapplicablecodes.
• TheCarrier30HXCunitsaredesignedandbuilttoensureconformancewith
localcodes.TherecommendationsofEuropeanstandardEN60204-1
(correspondstoIEC60204-1)(machinesafety-electricalmachine
components-part1:generalregulations)arespecicallytakenintoaccount,
whendesigningtheelectricalequipment.

CircuitBhasdisconnectswitchesandbranchsections,designedtosupplythe
evaporatorandcondenserpumppowerinput.

• GenerallytherecommendationsofIEC60364areacceptedascompliance
withtherequirementsoftheinstallationdirectives.ConformancewithEN
60204-1isthebestmeansofensuringcompliancewiththeMachinesDirective
and§1.5.1.
• AnnexBofEN60204-1describestheelectricalcharacteristicsusedforthe
operationofthemachines.
1. Theoperatingenvironmentforthe30HXCunitsisspeciedbelow:
a. Environment*-EnvironmentasclassiedinIEC60364§3:
- ambienttemperaturerange:+5°Cto+40°C,classAA4
- humidity range (non-condensing)*:
50% relative humidity at 40°C
90%relativehumidityat20°C
- altitude:≤2000m
- indoor installation*
- presenceofwater:classAD2*(possibilityofwaterdroplets)
- presenceofhardsolids,classAE2*(nosignicantdustpresent)
- presenceofcorrosiveandpollutingsubstances,classAF1(negligible)
- vibrationandshock,classAG2,AH2
b. Competenceofpersonnel,classBA4*(trainedpersonnel-IEC60364)
2. Powersupplyfrequencyvariation:±2Hz.
3. Theneutral(N)linemustnotbeconnecteddirectlytotheunit(ifnecessaryuse
atransformer).
4. Overcurrentprotectionofthepowersupplyconductorsisnotprovidedwiththe
unit.
5. Thefactory-installeddisconnectswitch(es)/circuitbreaker(s)is(are)ofatype
suitableforpowerinterruptioninaccordancewithEN60947(correspondsto
IEC60947).
6. TheunitsaredesignedforconnectiontoTNnetworks(IEC60364).ForIT
networkstheearthconnectionmustnotbeatthenetworkearth.Providealocal
earth, consult competent local organisations to complete the electrical
installation.



* TheprotectionlevelrequiredtoconformtothisclassisIP21B(accordingto
referencedocumentIEC60529).All30HXCunitsareprotectedtoIP23Cand
fullthisprotectioncondition.