APPENDIX A -- LOCAL DISPLAY TABLES (cont)
MODE -- SET POINTS
EXPANSION
COOLING SETPOINTS
Cooling Setpoint 1
Cooing Setpoint 2
Ice Setpoint
Current No Reset Val
Current Full Reset Val
Delta T No Reset Temp
Delta T Full Reset Temp
OAT No Reset Temp
OAT Full Reset Temp
Space T No Reset Temp
Space T Full Reset Temp
Degrees Cool Reset
Cool Changeover Setpt
Cool Ramp Loading
HEATING SETPOINTS
Heating Setpoint 1
Heating Setpoint 2
Current to Reset Val
Current Full Reset Val
Delta T No Reset Temp
Delta T Full Reset Temp
OAT No Reset Temp
OAT Full Reset Temp
Degrees Heat Reset
Heat Changeover Setpt
Heat Ramp Loading
MISC SETPOINTS
Switch Limit Setpoint 1
Switch Limit Setpoint 2
Switch Limit Setpoint 3
Water Val Cond Stp
Heat Reclaim Setpoint
Reclaim Deadband
UNITS RANGE COMMENT
XXXX.X
(deg F/deg C)
XXXX.X
(deg F/deg C)
XXXX.X
(deg F/deg C)
XX.X (mA)
XX.X (mA)
XXX.X (AF/AC)
xxx.x (AF/AC)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XX.X (AF/AC)
XX.X
(deg F/deg C)
X.X
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XX.X (mA)
XX.X (mA)
XXX.X (AF/AC)
XXX.X (AF/AC)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XX.X (AF/AC)
XX.X
(deg F/deg C)
X.X
xxx (%)
xxx (%)
xxx (%)
XXX.X
(deg F/deg C)
XXX.X
(deg F/deg C)
XX.X (AF/AC)
-20-70 F
(-29-21 C),
Default = 44.0
20-70 F
(-29-21 C),
Default = 44.0
-20-70 F
( 29-21 C),
Default = 44.0
0-20,
Default = 0
0-20,
Default - 0
0-125 F
(0-69.4 C),
Default = 0
0-125 F
(0-69.4 C),
Default - 0
0-125 F
(-18-52 C),
Default = 14.0
0-25 F
( 18-52 C),
Default = 14.0
0-125 F
(-18-52 C),
Default- 14.0
0-125 F
(-18-52 C),
Default = 14.0
-30-30 F
-16.7-16.7 C),
Default - 0
Default = 75.0
0.2-2.0 AF
(0.1-1.1 AC),
Default = 1.0
Default = 100
Default = 100
Default = 0
Default = 0
Default - 0
Default - 0
Default - 14.0
Default = 14.0
Default = 0
Default = 64
Default = 1.0
0-100,
Default- 100
0-100,
Default- 100
0-100,
Default = 100
80-140 F
(26.7-60 C)
Default - 122
Default = 9.0
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
Not supported.
WRITE
STATUS
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
CCN TABLE
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
SETPOINT
CCN POINT
cspl
csp2
ice sp
v cr no
v crfu
dt cr no
dt crfu
oatcr no
oatcrfu
spacr no
spacr fu
cr deg
cauto sp
cramp sp
HSR1
HSR2
v hr no
v hr fu
dt hr no
dt hrfu
oathr no
oathrfu
DGRH
hautosp
hramp sp
lira spl
lira sp2
lira sp3
w sct sp
rsp
hrdeadb
PAG E
NO.
30, 42
30, 50
30, 50.
51
32
32
31
31
31
31
31
31
31
15, 20,
5O
32
32
92

Table of Contents

Other manuals for Carrier 30XA080-500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 30XA080-500 and is the answer not in the manual?

Carrier 30XA080-500 Specifications

General IconGeneral
BrandCarrier
Model30XA080-500
CategoryChiller
LanguageEnglish

Related product manuals