Alarms tab
Dead Controller Timeout
BACnet/SC Certificate
Expiration
The current status of the alarm
Enable To Off-Normal Event
Clear this checkbox to disable Alarm or Return to off-normal messages of this type
from the i-Vu® XT Router.
Clear this checkbox to disable Alarm or Return to normal messages of this type
from the i-Vu® XT Router.
Specifies the delay between the onset of the Off-Normal condition and the
reporting of the alarm to the i-Vu® application.
Short message shown when this type of alarm is generated.
A BACnet alarm's Notification Class defines:
• Alarm priority for Alarm, Fault, and Return to Normal states
• Options for BACnet alarm acknowledgment
• Where alarms should be sent (recipients)
Alarms in the i-Vu® application use Notification Class #1. The i-Vu® application is
automatically a recipient of these alarms.
A unique alphanumeric string that defines the BACnet object.
If a certificate is within this number of days of expiring, it will appear yellow in the
Certificate Management table.
A weekly alarm will be triggered in the i-Vu® application when one of the router’s
BACnet/SC certificates is in this state.
If a certificate is within this number of days of expiring, it will appear red in the
Certificate Management table.
A daily alarm will be triggered in the i-Vu® application when one of the router’s
BACnet/SC certificates is in this state.