Appendix C: RTU Open Points/Properties on the Equipment Touch
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
99
Point Name/Description
Range
Minimum Cooling SAT
In cooling mode, the cooling outputs are controlled so that the
supply air temperature does not drop below this value.
D:
R:
50°F (10°C)
45 to 75°F
(7.2 to 23.9°C)
Maximum Heating SAT
In heating mode, the heating outputs are controlled so the
supply air temperature does not rise above this value.
D:
R:
120°F
85 to 150°F
Supply Fan Service Alarm Timer
A Supply Fan Runtime alarm is generated when the
supply fan run hours exceed this value. Set to 0 to disable.
D:
R:
600 hr
0 to 9999 hr
Filter Service Alarm Timer
The amount of time the fan will run before generating a
Filter Alarm
. Set to 0 to disable the alarm and reset accumulated fan hours.
D:
R:
600 hr
0 to 9999 hr
Pushbutton Override
Enables or disables the use of a pushbutton override from a
local space temperature sensor.
D:
R:
Enable
Disable/Enable
Setpoint Adjustment
Enables or disables the setpoint adjustment mechanism on the
local space sensor. Not displayed unless ZS or SPT sensor is connected.
D:
R:
Enable
Disable/Enable
Setpoint Adjustment Range
- The maximum amount that a user can adjust the setpoint
on the local ZS or SPT sensor. Not displayed unless ZS or SPT sensor is connected.
D: 5
°F (2.7 °C)
Cooling Lockout Temperature
Cooling is inhibited below this outdoor air temperature. D:
R:
45°F (7.2°C)
-65 to 80°F
(-53.9 to 26.6°C)
Economizer High OAT Lockout
Temp
The outdoor air temperature above which
economizer cooling is inhibited.
D:
R:
75°F (23.9°C)
55 to 80°F
(12.7 to 26.6°C)
Heating Lockout Temperature
Heating is inhibited above this outdoor air
temperature.
D:
R:
65°F (18.3°C)
35 to 150°F
(1.6 to 65.5°C)
Pre Occupancy Purge
Enables or disables the use of a purge cycle immediately prior
to the start of a scheduled occupied period.
D:
R:
Disable
Disable/Enable
Purge Time
The maximum amount of time used for a pre-occupancy purge. D:
R:
60 minutes
0 to 240 minutes
Unocc Free Cool
Enables or disables the use of the economizer to provide unoccupied
free cooling (NTFC).
D:
R:
Disable
Disable/Enable

Table of Contents

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals