Appendix C: RTU Open Points/Properties on the Equipment Touch
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
95
Startup Wizard
Navigation:
Equipment Touch:
Startup Wizard
Point Name/Description
Range
Unit Type
The type of equipment that the RTU Open is controlling.
Options:
Heat/Cool
Standard rooftop air handling unit.
LC Weather Expert
A special factory-supplied 3-stage cooling unit
HP O/B Ctrl
Heat Pump application, uses reversing valve output to control heating
and cooling.
HP Y1/W1 Ctrl
Carrier Heat Pump application only.
D:
R:
Heat/Cool
Heat/Cool
LC WeatherExpert™
HP O/B Ctrl
HP Y1/W1 Ctrl
Heat Type
The type of heating used by the unit.
D:
R:
Electric
Electric/Gas
Heat Stages
The number heat stages. D:
R:
2
1 / 2 /0 (no heating)
Compressor Stages
The number of mechanical cooling stages.
D:
R:
One Stage
One Stage
Two Stages
Fan Control
The type of fan control used on this unit.
Automatically set to
Variable Speed
if
Unit Type
is set to
LC WeatherExpert™
.
D:
R:
Single Speed
Single Speed
Two Speed
Variable Speed
Economizer Exists
Set to
Yes
to enable economizer control for units equipped with an
economizer damper.
D:
R:
No
No/Yes
Economizer High OAT Lockout
Temp
The outdoor air temperature above which
economizer cooling is inhibited.
D:
R:
75°F (23.9°C)
55 to 80°F
(12.7 to 26.6°C)
Vent Dmpr Pos / DCV Min Pos
The minimum outdoor air damper position maintained
during occupied periods.
D:
R:
20% Open
0 to 100%
Economizer Purge Min Pos
The minimum outdoor air damper position maintained
during an unoccupied purge cycle when the Pre-Occ Purge mode is active.
D:
R:
40% Open
0 to 100% Open
Low Fan Econ Min Pos
The minimum outdoor air damper position maintained during
occupied periods when the fan is running at low speed (if configured for 2-speed fan
control) or the minimum VFD speed (if configured for variable speed fan control).
D:
R:
33% Open
0 to 100% Open
RH Control
Enables dehumidification control if an RH sensor or humidistat is
available and the unit has the Humidi-MiZer™ dehumidification option installed.
D:
R:
Disable
Disable/Enable
DCV Control
Enables demand controlled ventilation (DCV) if valid CO
2
sensor value is
available and the unit has an economizer installed.
D:
R:
Disable
Disable/Enable

Table of Contents

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals