Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
76
>
>
>
Occupied Alarm Hysteresis
– This value is added to the occupied high effective setpoint
and subtracted from the occupied low effective setpoint to establish the occupied high
and low limits that the space temperature must exceed before an occupied SPT alarm
is generated. The alarm returns to normal when the space temperature drops below the
high effective setpoint or rises above the low effective setpoint.
D:
R:
5
°F (2.7 °C)
0 to 20 °F
(0 to 11.1
°C)
– Determines the amount of delay before an occupied space
temperature alarm is generated when the controller transitions to the occupied mode.
The delay time equals this value multiplied by the difference between the sensor
temperature and occupied alarm setpoint plus 15 minutes.
D:
R:
10 minutes
0 to 60 minutes
Unoccupied Low SPT Alarm Limit
–The value that the space temperature must drop
below to generate a
in the unoccupied mode. There is a
fixed hysteresis of 1
°F (.5 °C) for return to normal.
D:
R:
45°F (7.2°C)
35 to 90°F
(1.6 to 32.2°C)
Unoccupied High SPT Alarm Limit
– The value that the space temperature must exceed
to generate a
in the unoccupied mode. There is a fixed
hysteresis of 1
°F (.5 °C) for return to normal.
D:
R:
95°F (35°C)
45 to 100°F
(7.2 to 37.7°C)
Supply Air Temperature Alarm
– The value that the supply air temperature must drop below to
generate a
. There is a fixed hysteresis of 5 °F (2.7 °C) for
return to normal.
D:
R:
38°F (3.3°C)
15 to 90°F
(-9.4 to 32.2°C)
– The value that the supply air temperature must exceed to
generate a
. There is a fixed hysteresis of 5 °F (2.7 °C) for
return to normal.
D:
R:
160°F (71.1°C)
90 to 175°F
(32.2 to 79.4°C)
Occupied High RH Alarm Limit
– The value that the relative humidity sensor must
exceed to generate a
in the occupied mode if
is set
to
. There is a fixed hysteresis of 5%rh for return to normal.
D:
R:
70%rh
0 to 100%rh
– Determines the amount of delay before an occupied RH
alarm is generated when the controller transitions to the occupied mode. The delay time
equals this value multiplied by the difference between the sensor RH value and the
occupied RH setpoint plus 15 minutes.
D:
R:
5 minutes
0 to 30 minutes
Unoccupied High RH Alarm Limit
– The value that the relative humidity sensor must
exceed to generate a
alarm in the unoccupied mode if
is set to
. There is a fixed hysteresis of 5%rh for return to normal.
D:
R:
100%rh
0 to 100%rh