Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
77
Point Name/Description
Default/Range
Low RH Alarm Limit
The value that the relative humidity sensor must drop below to
generate a
Space Humidity Alarm
in either the unoccupied or occupied modes if
RH
Control
is set to
Enable
. There is a fixed hysteresis of 5%rh for return to normal.
D:
R:
30%rh
0 to 100%rh
IAQ/Ventilation Alarm
Occupied High CO2 Alarm Limit
The value that the CO
2
sensor must exceed to
generate an
IAQ Alarm
in the occupied mode. There is a fixed hysteresis of 100ppm for
return to normal. Requires a valid
Indoor Air Quality CO2
sensor value and
IAQ Control
is set to
Enable
.
D:
R:
1200ppm
0 to 9999 ppm
Alarms Displayed on ZS or SPT Sensor
You can individually select items below to show the alarm indicator on the ZS or SPT
sensor.
Range
Fire / Smoke Shutdown
Alarm
If set to display, shows the alarm indicator on the
communicating zone sensors with display, if the fire shutdown circuit trips.
D:
R:
Ignore
Ignore/Display
Stuck Gas Valve Alarm
If set to display, shows the alarm indicator on the
communicating zone sensors with display, if the fire shutdown circuit trips.
D:
R:
Ignore
Ignore/Display
Compressor Safety/Chain Alarm
If set to display, shows the alarm indicator on the
communicating zone sensors with display, if the safety chain circuit trips.
D:
R:
Ignore
Ignore/Display
Space Temperature High/Low Alarm
If set to display, shows the alarm indicator on
the communicating zone sensors with display, if the space temperature sensor exceeds
the high or low alarm limit.
D:
R:
Ignore
Ignore/Display
Space Indoor Air CO2 High Alarm
If set to display, shows the alarm indicator on the
communicating zone sensors with display, if the occupied CO2 level exceeds the
configured high alarm limit.
D:
R:
Ignore
Ignore/Display
Space Relative Humidity High Alarm
If set to display, shows the alarm indicator on
the communicating zone sensors with display, if a valid space relative humidity sensor
exceeds the configured alarm limits.
D:
R:
Ignore
Ignore/Display
Supply Fan Failure Alarm
If set to display, shows the alarm indicator on the
communicating zone sensors with display, if the supply fan is not operating when
commanded on.
D:
R:
Ignore
Ignore/Display
Supply Air Temperature Low OR High Alarm
If set to display, shows the alarm
indicator on the communicating zone sensors with display, if the supply air temperature
exceeds the configured alarm limits.
D:
R:
Ignore
Ignore/Display
Maintenance Displayed on ZS Sensor

Table of Contents

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals