EasyManuals Logo
Home>Carrier>Controller>RTU Open v3

Carrier RTU Open v3 User Manual

Carrier RTU Open v3
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
Installing the RTU Open
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
13
Wiring inputs and outputs
RTU Open Inputs and Outputs Table
Channel
Number
Type
Signal
Function
Part Number
Wire and
Terminal
Numbers
Alternate
Terminals
Input 1
AI
4-20 mA
CO2
OAQ
Space Relative Humidity
33ZCT55CO2 33ZCT56CO2
33ZCSPTCO2-01
33ZCSPTCO2LCD-01
w/ 33ZCASPCO2
33ZCSENSRH-02
J4
- 5 & 6
N/A
Input 2
AI
4-20 mA
CO2
OAQ
Space Relative Humidity
33ZCT55CO2 33ZCT56CO2
33ZCSPTCO2-01
33ZCSPTCO2LCD-01
w/ 33ZCASPCO2
33ZCSENSRH-02
J4
-
2 & 3
N/A
Input 3
BI
24 Vac
Compressor Safety **
2
Fan Status
Filter Status
Remote Occupancy
Door Contact
N/A
CRSTATUS005A00
CRSTATUS005A00
Field-supplied
Field-supplied
J1
-
2
J5
- 5 & 6 ***
Input 4
BI
24 Vac
Safety Chain *
N/A
J1 - 9
N/A
Input 5
BI
24 Vac
Fire Shutdown **
1,
2
Fan Status
Filter Status
Remote Occupancy
Door Contact
Field-supplied
CRSTATUS005A00
CRSTATUS005A00
Field-supplied
Field-supplied
J1 - 10
J5 - 3 & 4 ***
Input 6
AI
10K
Thermistor
Supply Air Temperature
33ZCSENSAT 33ZCSENDAT
J2
- 1 & 2
N/A
Input 7
AI
10K
Thermistor
Outside Air Temperature
33ZCSENOAT
J2
- 3 & 4
N/A
Input 8
BI
24 Vac
Enthalpy **
Fan Status
Filter Status
Remote Occupancy
Door Contact
33SENTHSW
CRSTATUS005A00
CRSTATUS005A00
Field-supplied
Field-supplied
J2 - 6 & 7
J5 - 1 & 2 ***
Input 9
BI
24 Vac
IGC Input****
Humidistat **
Fan Status
Filter Status
Remote Occupancy
Door Contact
--HL--38MG-029
CRSTATUS005A00
CRSTATUS005A00
Field-supplied
Field-supplied
J5
- 7 & 8
N/A
Input 10
AI
10K
Thermistor
Space Temperature
33ZCT55SPT 33ZCT56SPT
33ZCT59SPT
J20
- 1 & 2
N/A
Input 11
AI
100K
Thermistor
Space Temperature
Setpoint Adjust
33ZCT56SPT 33ZCT59SPT
J20
- 3 & 4
N/A
Rnet
AI
ZS sensors
Wireless Adapter for
wireless sensors
Equipment Touch
TruVu™ ET Display
See Wiring devices to the Rnet
port.
J13 - 1, 2, 3,
4
N/A
AO - 1
AO
4-20 mA
Economizer
Actuator-Field-supplied
J2
- 5 & 4
N/A

Table of Contents

Other manuals for Carrier RTU Open v3