EasyManuals Logo
Home>Carrier>Controller>RTU Open v3

Carrier RTU Open v3 User Manual

Carrier RTU Open v3
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
Installing the RTU Open
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
35
Wiring an enthalpy switch
Outdoor Air - Part #33CSENTHSW
Return air - Part #33CSENTSEN
The 33CSENTHSW is an outdoor air enthalpy switch/receiver. This control determines the suitability of the outdoor
air as a cooling source, based on the heat content of the air. Differential enthalpy control requires installing a
33CSENTSEN enthalpy sensor in the rooftop unit's return air duct.
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length: 500 feet (152 meters)
To wire an enthalpy switch (outdoor air) to the controller
An enthalpy switch is typically mounted in the outdoor air inlet.
Wiring diagram for a field-installed enthalpy switch:

Table of Contents

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals