Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
62
All possible points and properties that are available on the i-Vu® or Field Assistant
tab are defined in
the following pages.
See Appendix C (page 93) for the points and properties available on the Equipment Touch interface.
Engineering units shown in this document in the defaults and ranges are strictly for reference. You must
enter an integer only.
>
>
– The controller's current status. R: Disabled
Test
Run
– The controller's current operating mode. R: Off
Fan Only
Economizer Cooling
Cooling
Heating
Dehumidification
Test
Shutdown
Unocc Free Cooling
Fire Shutdown
IAQ Override
Pre-occ Purge
IGC Override
– The current fan status if an input is configured for
. R: Off/Running
The current commanded fan speed if
is set to
. R: Off/Low/High
– The current commanded output to the VFD to control the fan's speed
if
is set to
.
R: Off/Low/High
– The space temperature value currently used for
control.
R: -56 to 245°F
(-48.9 to 118.3°C)
– Displays the current supply air temperature. R: -56 to 245°F
(-48.9 to 118.3°C)
– The outdoor air temperature used for control. R: -56 to 245°F
(-48.9 to 118.3°C)
– The current space relative humidity if a valid value exists
either as a connected ZS sensor with RH or a hardware sensor connected to this
controller (
>
>
(or
)
is set to
)
or a value received through the Network or Linkage.
R: 0 to 100%rh
Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant