Wiring a relative humidity sensor
Wall and duct sensor - Part #33ZCSENSRH-02 and 33ZCSENDRH-02
The Relative Humidity (RH) sensor may be used for zone humidity control (dehumidification) when applied to a
Carrier rooftop unit equipped with the Humidi-MiZer™ option. On units not equipped for dehumidification, the
sensor monitors humidity, but provides no control.
NOTE
You cannot use a relative humidity sensor when using both a CO
2
and OAQ sensor on the controller.
Wiring specifications
Cable from sensor to controller: If <100 ft (30.5 meters) 22 AWG, unshielded
If >100 ft (30.5 meters) 22 AWG, shielded
Maximum length: 500 feet (152 meters)
To wire a separate dedicated RH sensor to the controller
1 Strip the outer jacket from the cable for at least 4 inches (10.2 cm). Strip .25 inch (.6 cm) of insulation from
each wire.
2 Wire the sensor to the controller. See diagram below.
3 Apply power and verify sensor readings.
NOTE
Sensor may be terminated at Input 1 or 2.

Table of Contents

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals