Appendix C: RTU Open Points/Properties on the Equipment Touch
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
102
Point Name/Description
Default/Range
Space Humidity Alarm
Occupied High RH Alarm Limit
The value that the relative humidity sensor must
exceed to generate a
Space Humidity Alarm
in the occupied mode if
RH Control
is set
to
Enable
. There is a fixed hysteresis of 5%rh for return to normal.
D:
R:
70%rh
0 to 100%rh
Unoccupied High RH Alarm Limit
The value that the relative humidity sensor must
exceed to generate a
Space Relative Humidity
alarm in the unoccupied mode if
RH
Control
is set to
Enable
. There is a fixed hysteresis of 5%rh for return to normal.
D:
R:
100%rh
0 to 100%rh
Low RH Alarm Limit
The value that the relative humidity sensor must drop below to
generate a
Space Humidity Alarm
in either the unoccupied or occupied modes if
RH
Control
is set to
Enable
. There is a fixed hysteresis of 5%rh for return to normal.
D:
R:
30%rh
0 to 100%rh
IAQ/Ventilation Alarm
Occupied High CO2 Alarm Limit
The value that the CO
2
sensor must exceed to
generate an
IAQ Alarm
in the occupied mode. There is a fixed hysteresis of 100ppm for
return to normal. Requires a valid
Indoor Air Quality CO2
sensor value and
IAQ Control
is set to
Enable
.
D:
R:
1200ppm
0 to 9999 ppm
Maintenance - Equipment Touch
Navigation:
Equipment Touch:
Properties > Control Program > Maintenance
Point Name/Description
Default/Range
Unit
Occupancy Status
The controller's occupancy status as determined by a network
schedule, a local schedule, or a timed override.
R: Unoccupied/Occupied
Pre-Occ Purge
Indicates if the pre-occupancy purge cycle is active. R: Inactive/Active
Setpoint Adjustment
Indicates the amount of offset applied if you configured the
space sensor as a type of T56. Set the display value range in
Setpoint Adjustment
Range
.
R: _°F/C
Effective Heat Setpoint
The current heating setpoint. May include offsets from
configured occupied/unoccupied setpoints resulting from
Optimal Start
to
Demand
Limit
.
R: _°F/C
Effective Cool Setpoint
The current cooling setpoint. May include offsets from
configured occupied/unoccupied setpoints resulting from
Optimal Start
to
Demand
Limit
.
R: _°F/C
System Cooling Demand Level
The demand limit used by the control in cooling mode. R: 0 to 3
System Heating Demand Level
The demand level used by the control in heating
mode.
R: 0 to 3

Table of Contents

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals