Appendix C: RTU Open Points/Properties on the Equipment Touch
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
103
Active Compressor Stages –
The number of compressor stages currently operating. R: 0 to 2
The number of heating stages currently operating. R: 0 to 2
– The enthalpy status the controller receives through BACnet
communication.
R: High (0) / Low (1)
Reset Supply Fan Runtime Alarm
– Set to
to reset
to 0. D:
R:
Run
Run/Clear
Reset Filter Runtime Alarm
– Set to
to reset
to 0. D:
R:
Run
Run/Clear
– Determines the occupancy state of the controller and can be set over the
network by another device or third party BAS.
Options:
– Occupancy is determined by a configured schedule.
– The controller is always in the occupied mode.
– The controller is always in the unoccupied mode.
If
is set to either
or
, the
routine
is automatically disabled.
D:
R:
Inactive
Inactive
Occupied
Unoccupied
–
indicates if a user pushed the sensor's override button to
override the occupancy state.
R: Off/Active
– The amount of time remaining in an override period. R: 0 to 240 minutes
– The controller's occupancy status based on the local schedule. R: Unoccupied/Occupied
R: OFF
WARMUP
HEAT
COOL
FREECOOL
PRESSURIZE
EVAC
VENT
NOT ACTIVE