Appendix C: RTU Open Points/Properties on the Equipment Touch
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
100
Setpoints - Equipment Touch
– Green
The heating setpoint the controller maintains while in occupied mode.
D:
R:
70°F (21.1°C)
40 to 90°F
(4.4 to 32.2°C)
– Green
The cooling setpoint the controller maintains while in occupied mode.
D:
R:
76°F (24.4°C)
55 to 99°F
(12.7 to 37.2°C)
– Gray
The heating setpoint the controller maintains while in unoccupied mode.
D:
R:
55°F (12.7°C)
40 to 90°F
(4.4 to 32.2°C)
– Gray
The cooling setpoint the controller maintains while in unoccupied mode.
D:
R:
90°F (32.2°C)
45 to 99°F
(7.2 to 37.2°C)
– The method used to change from unoccupied to occupied setpoint.
Options:
– Unit will not change to occupied setpoint until the scheduled time or the unit goes into an
occupied mode. Setpoints do not ramp, but change immediately from unoccupied to occupied
values.
– Unit changes to occupied setpoints at a variable time prior to the occupied
time, which is calculated by the current difference between space temperature and the
appropriate heating or cooling setpoint. At that time, the setpoints do not ramp, but change
immediately from unoccupied to occupied values.
– Unit gradually changes to occupied setpoints by adjusting the
unoccupied setpoints over a specified period of time to achieve the occupied setpoint by the time
scheduled occupancy begins.
D:
R:
Temperature
Compensated
None
Temperature
Compensated
Learning
Adaptive
Heat Start K factor (min/deg)
– If
is
, this is the time in
minutes per degree that the equipment starts before the occupied period when the space
temperature is below the occupied heating setpoint (including any setpoint offset).
D:
R:
15.00
0 to 99
Cool Start K factor (min/deg)
– If
is
, this is the time in
minutes per degree that the equipment starts before the occupied period when the space
temperature is above the occupied cooling setpoint (including any setpoint offset).
D:
R:
15.00
0 to 99