Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
88
Point Name/Description
Range
Analog Input Configuration
Indicates if a duplicate configuration exists at the analog
Input 1 & 2 Functions.
R: Normal/Alarm
Supply Fan Runtime
Indicates if the supply fan runtime exceeds the value of the
Supply Fan Service Alarm Timer
.
R: Normal/Alarm
Compressor 1 Runtime
Indicates if the compressor 1 runtime exceeds the value of
the
Compressor 1 Service Alarm Timer
.
R: Normal/Alarm
Compressor 2 Runtime
Indicates if the compressor 1 runtime exceeds the value of
the
Compressor 2 Service Alarm Timer
.
R: Normal/Alarm
Airside Linkage
Indicates if Linkage has failed in a zoned system using Linkage. R: Normal/Alarm
Linkage
Navigation:
i-Vu® / Field Assistant:
Properties
>
Control Program
>
Configuration
>
Service Configuration
Point Name/Description
Range
Linkage
Collector
Allows access to the Collector's details.
Click to see the following properties on the
Summary
tab of microblock popup:
Application Type
This parameter indicates the type of Linkage application.
(Display only)
D: Airside Linkage
Application Instance
Should always be
1
for i-Vu®/Field Assistant Systems.
NOTE
If using a CCN and BACnet System (i.e., CCN Air Terminal to BACnet Air
Source), the
Application Instance
can be
1
,
2
,
3
, or
4
,
depending on the
number of air sources used in the system.
D:
R:
1
1
2
3
4
Maximum Providers
Indicates the maximum configurable size of the VVT
zoning system. (Display only - fixed value)
D: 64
Number of Providers
Must be set to
0
. D: 0
Input Values
Indicates the maximum number of parameters in the collector
array for each device. (Display only)
D: 24
Feedback Values
Indicates the maximum number (4 possible) of
parameters in the collector array for any RTU Open. (Display only - fixed
value)
D: 8
Feedback Update Time
Indicates the typical update rate of this application.
(Display only - fixed value)
D: 60 sec
Input Expiration Time
Indicates the maximum time that the data received
from the master zones, since the last refresh, is considered as valid . (Display
only - fixed value)
D: 300 sec

Table of Contents

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals