Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
74
Point Name/Description
Range
English
Metric
Green
The amount the zone’s learned heating capacity is adjusted when the Learning
Adaptive Optimal Start algorithm runs, when the zone’s thermographic color at
occupancy is green.
D:
R:
0.0600
0 to 1
.0333
SpGrn
The amount the zone’s learned cooling capacity is adjusted when the Learning
Adaptive Optimal Start algorithm runs, when the zone’s thermographic color at
occupancy is green.
D:
R:
0.0600
0 to 1
.0333
Yellow
The amount the zone’s learned cooling capacity is adjusted when the Learning
Adaptive Optimal Start algorithm runs, when the zone’s thermographic color at
occupancy is yellow.
D:
R:
0.0600
0 to 1
.0333
Orange
The amount the zone’s learned cooling capacity is adjusted when the
Learning Adaptive Optimal Start algorithm runs, when the zone’s thermographic color at
occupancy is orange.
D:
R:
0.1300
0 to 1
.0722
Red
The amount the zone’s learned cooling capacity is adjusted when the Learning
Adaptive Optimal Start algorithm runs, when the zone’s thermographic color at
occupancy is red.
D:
R:
0.1900
0 to 1
.1055
Heating
(Occupied or Unoccupied, depending on mode) The current programmed
Heating
setpoint adjusted by any offset that may be in effect.
R: 0 to 120°F
(-17.7 to
48.9°C)
Cooling
(Occupied or Unoccupied, depending on mode) The current programmed
Cooling
setpoint adjusted by any offset that may be in effect.
R: 0 to 120°F
(-17.7 to
48.9°C)
Learned cooling capacity
The cooling capacity learned by Learning Adaptive Optimal Start that
is required to bring the space temperature down to the occupied cooling setpoint prior to the
occupied time.
R: _°F/C
Learned heating capacity
The heating capacity learned by Learning Adaptive Optimal Start that
is required to bring the space temperature up to the occupied heating setpoint prior to the
occupied time.
R: _°F/C
Min Setpoint Separation
Minimum separation that must be maintained between the heating
and cooling setpoints.
R: _°F/C
Optimal Start
The number of hours prior to occupancy, at which the Optimal Start function may
begin to adjust the effective setpoints to achieve the occupied setpoints by the time scheduled
occupancy begins. Enter 0 to disable Optimal Start.
NOTE
Optimal Start is automatically disabled when occupancy is controlled by a network write to
the controller's keypad_ovrde variable. (Display name:
BAS On/Off
, in
Properties
>
Control
Program
>
Maintenance
>
Occupancy
>
BAS On/Off
. or when utilizing
Airside Linkage
or the
System Occupancy Network Variable
.
D:
R:
4 hr
0 to 4 hrs

Table of Contents

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals