Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
74
– The amount the zone’s learned heating capacity is adjusted when the Learning
Adaptive Optimal Start algorithm runs, when the zone’s thermographic color at
occupancy is green.
D:
R:
0.0600
0 to 1
.0333
– The amount the zone’s learned cooling capacity is adjusted when the Learning
Adaptive Optimal Start algorithm runs, when the zone’s thermographic color at
occupancy is green.
D:
R:
0.0600
0 to 1
.0333
– The amount the zone’s learned cooling capacity is adjusted when the Learning
Adaptive Optimal Start algorithm runs, when the zone’s thermographic color at
occupancy is yellow.
D:
R:
0.0600
0 to 1
.0333
– The amount the zone’s learned cooling capacity is adjusted when the
Learning Adaptive Optimal Start algorithm runs, when the zone’s thermographic color at
occupancy is orange.
D:
R:
0.1300
0 to 1
.0722
– The amount the zone’s learned cooling capacity is adjusted when the Learning
Adaptive Optimal Start algorithm runs, when the zone’s thermographic color at
occupancy is red.
D:
R:
0.1900
0 to 1
.1055
(Occupied or Unoccupied, depending on mode) The current programmed
setpoint adjusted by any offset that may be in effect.
R: 0 to 120°F
(-17.7 to
48.9°C)
(Occupied or Unoccupied, depending on mode) The current programmed
setpoint adjusted by any offset that may be in effect.
R: 0 to 120°F
(-17.7 to
48.9°C)
– The cooling capacity learned by Learning Adaptive Optimal Start that
is required to bring the space temperature down to the occupied cooling setpoint prior to the
occupied time.
R: _°F/C
– The heating capacity learned by Learning Adaptive Optimal Start that
is required to bring the space temperature up to the occupied heating setpoint prior to the
occupied time.
R: _°F/C
– Minimum separation that must be maintained between the heating
and cooling setpoints.
R: _°F/C
– The number of hours prior to occupancy, at which the Optimal Start function may
begin to adjust the effective setpoints to achieve the occupied setpoints by the time scheduled
occupancy begins. Enter 0 to disable Optimal Start.
Optimal Start is automatically disabled when occupancy is controlled by a network write to
the controller's keypad_ovrde variable. (Display name:
, in
>
>
>
>
. or when utilizing
or the
System Occupancy Network Variable
.
D:
R:
4 hr
0 to 4 hrs