Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
84
– The humidity status determined by a humidistat. R: High/Low
– Displays the current filter condition to the filter input if that option is
configured.
R: Clean/Dirty
– Displays the state of the door contact switch if that option is
configured.
R: Off/On
Displays the state of the
input status. An
state
indicates a flame is present.
R: Off/Active
Reset Supply Fan Runtime Alarm
– Set to
to reset
to 0. D:
R:
Run
Run/Clear
Reset Comp 1 Runtime Alarm
– Set to
to reset
to 0. D:
R:
Run
Run/Clear
Reset Comp 2 Runtime Alarm
– Set to
to reset
to 0. D:
R:
Run
Run/Clear
Reset Filter Runtime Alarm
– Set to
to reset
to 0. D:
R:
Run
Run/Clear
– Determines the occupancy state of the controller and can be set over the
network by another device or third party BAS.
Options:
– Occupancy is determined by a configured schedule.
– The controller is always in the occupied mode.
– The controller is always in the unoccupied mode.
If
is set to either
or
, the
routine
is automatically disabled.
D:
R:
Inactive
Inactive
Occupied
Unoccupied
–
indicates if a user pushed the sensor's override button to
override the occupancy state.
R: Off/Active
–
indicates an external contact is controlling the occupancy
state.
R: Off/On
– The amount of time remaining in an override period. R: 0 to 240 minutes
– The controller's occupancy status based on the local schedule. R: Unoccupied/Occupied
– The total number of hours that the supply fan relay has been
energized since the runtime was last reset to 0 using
Reset Supply Fan Runtime Alarm
.
R: __ hr
– The total number of hours that the Compressor 1 relay has
been energized since the runtime was last reset 0 using
Reset Comp 1 Runtime Alarm
.
R: __ hr