Appendix A: RTU Open Points/Properties in i-Vu®/Field Assistant
RTU Open v3 CARRIER CORPORATION ©2019
Installation and Start-up Guide All rights reserved
84
Point Name/Description
Default/Range
Humidistat Input Status
The humidity status determined by a humidistat. R: High/Low
Filter Status
Displays the current filter condition to the filter input if that option is
configured.
R: Clean/Dirty
Door Contact Status
Displays the state of the door contact switch if that option is
configured.
R: Off/On
IGC Override
Displays the state of the
IGC Override
input status. An
Active
state
indicates a flame is present.
R: Off/Active
Reset Supply Fan Runtime Alarm
Set to
Clear
to reset
Supply Fan Runtime
to 0. D:
R:
Run
Run/Clear
Reset Comp 1 Runtime Alarm
Set to
Clear
to reset
Compressor 1 Runtime
to 0. D:
R:
Run
Run/Clear
Reset Comp 2 Runtime Alarm
Set to
Clear
to reset
Compressor 2 Runtime
to 0. D:
R:
Run
Run/Clear
Reset Filter Runtime Alarm
Set to
On
to reset
Filter Runtime
to 0. D:
R:
Run
Run/Clear
Occupancy
BAS On/Off
Determines the occupancy state of the controller and can be set over the
network by another device or third party BAS.
Options:
Inactive
Occupancy is determined by a configured schedule.
Occupied
The controller is always in the occupied mode.
Unoccupied
The controller is always in the unoccupied mode.
NOTE
If
BAS On/Off
is set to either
Unoccupied
or
Occupied
, the
Optimal Start
routine
is automatically disabled.
D:
R:
Inactive
Inactive
Occupied
Unoccupied
Pushbutton Override
Active
indicates if a user pushed the sensor's override button to
override the occupancy state.
R: Off/Active
Occupancy Contact
ON
indicates an external contact is controlling the occupancy
state.
R: Off/On
Override Time Remaining
The amount of time remaining in an override period. R: 0 to 240 minutes
Schedule
The controller's occupancy status based on the local schedule. R: Unoccupied/Occupied
Runtime
Supply Fan Runtime
The total number of hours that the supply fan relay has been
energized since the runtime was last reset to 0 using
Reset Supply Fan Runtime Alarm
.
R: __ hr
Compressor 1 Runtime
The total number of hours that the Compressor 1 relay has
been energized since the runtime was last reset 0 using
Reset Comp 1 Runtime Alarm
.
R: __ hr

Table of Contents

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals