Page 50
SYSTEM COMPONENT ADDRESSING
ELFOENERGY / ELFOFRESH
2
ELFOEnergy - Parameters to be modified
Parameter
Mnemonic
Name
Description Value
164 Address ModBus serial address 2
165 Baud Rate Baud Rate (0=4800 / 1=9600) 1
166 Parity Parity 0=NO / 1=YES
0
ELFOFresh
2
- Parameters to be modified
Parameter
Mnemonic
Name
Description Value
165 Address ModBus serial address 3,4,5 or 6
166 Baud Rate Baud Rate (0=4800 / 1=9600) 1
167 Parity Parity 0=NO / 1=YES
0
1 Press
S
E
T
Parameter Value
1 0. 3
2 Enter the PASSWORD
+
-
0 3 2 1
3 Access parameter 164
1 6 4 X Y
4 Edit value as indicated in the table
+
-
1 6 4 2
5
Repeat the sequence for the other parameters indicated in the table
6
Save in the memory
Exit
S
E
T
1 0. 3
Units can be CPAN-U 70-650 (Elfofresh
2
) and / or
CPAN-U 17-51 (ElfoEnergy)
if one unit is present:
address = 3
if four units are presents:
First unit address = 3
Second unit address = 4
Third unit adress = 5
Fourth unit adress = 6