Page 74
PARAMETERS OF THE COMPONENTS
Below, we describe the parameters that are set by the autoconfiguration on the several components of the system; the list must be consid-
ered indicative and is an operative trace to be assessed, depending on the type and system configuration.
ELFOFresh CPAN-U 17-51
Modbus Parameter Value Description
43639 130 2 Enablement of modbus ambient probe
43647 138 2
Enablement of UR% ambient probe from Elfocontrol
2
161 0 Select the supervision mode
ELFOEnergy SMALL
Modbus Parameter Value Description
43627 163 1 Select the supervision mode
Enablement of DHW on Elfo Energy
Modbus Parameter Value Description
43686 50 2 Enablement of DHW production
43739 110 Introduce the excursion time of the valve
43576 119 1 DHW in heat and cool mode ; 2= if Wban
43569 140 1 Enablement of the plug-in card
ELFOFresh
2
CPAN-U 70-650
Modbus Parameter Value Description
1129 130 2 Enablement of the modbus ambient probe (always set to 2 )
1160 161 0 Select the supervision mode
1137 138 2
Enablement of UR% ambient probe from Elfocontrol
2
Mixing module
Modbus Parameter Value Description
1077 78 - - Enables compensation for dew in cooling mode. 0 = deactivate, 1 = activate
1084 85 90 sec. Time required to position VRad from closed to fully open
1085 86
400
num
Allows weighing the opening time of the valve,increase only if the mixing valve oscillates a lot
(typical of two-way valves)
GAIA (version AB and AC) - Anti-dew compensation enabling ( only in cooling)
Modbus Parameter Value Description
27 1 Anti-dew compensation enabling circuit 1 ; 0 = deactivate
892 1 Anti-dew compensation enabling circuit 2 ; 0 = deactivate
901 1 Anti-dew compensation enabling circuit 3 ; 0 = deactivate
HORUS
Modbus Parameter Value Description
12 - - Enable domestic hot water management 0= Not DHW, 1= DHW active
13 - - Enable boiler function + heat pump 0=No, 1= always, 2=disabled in DHW
24
1
25
358 Time for DHW valve opening (default 60)
Call from Elfocontrol
2