EasyManuals Logo
Home>ComAp>Marine Equipment>IG-NTC

ComAp IG-NTC User Manual

ComAp IG-NTC
67 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
Inteli NT GeCon MINT, SW Version 1.4, ©ComAp – June 2007
IGS-NT-GeCon-MINT-1.4.PDF
18
Gen-set operation states
Gen-set can operate in following states
Not ready Gen-set is not ready to start
Init After controller power supply switch on
Stopped No Running indication
Starting Waiting for ReadyToLoad signal
Running Waiting for GCB connection or start synchronizing
Soft load Gen-set power is ramping up
Loaded Gen-set is loaded
Soft unld Gen-set power is ramping down
Stopping Stopping procedure before the BI ReadyToLoad is opened.
Stopped Stopped - initial state – waiting for engine start
Breakers conditions
Brks Off GCB opened
Synchro Gen-set is synchronizing (bus voltage OK, GCB is
open)
MultIslOp Multiple Island - gen-set is running loaded in island
parallel mode (MCB is open, GCB is closed)
MultParOp Multiple Parallel – gen-set is running loaded in
mains parallel mode (MCB is closed, GCB is
closed)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IG-NTC and is the answer not in the manual?

ComAp IG-NTC Specifications

General IconGeneral
BrandComAp
ModelIG-NTC
CategoryMarine Equipment
LanguageEnglish

Related product manuals