Inteli NT GeCon MINT, SW Version 1.4, ©ComAp – June 2007
IGS-NT-GeCon-MINT-1.4.PDF
63
Ld recon delay [ s ] (FV)
The amount of time that the load has to be under Ld recon level before the next part of the load is
reconnected.
Step: 1 s
Range: 0 - 600 s
Force value: Yes
AutoLd recon [ DISABLED / ENABLED ] (FV)
Switch between manual and automatic reconnection of shedded load.
DISABLED Rising edge on this input resets controller to the lower stage, but only if the load is under the
Ld recon level. Ld recon delay is not important in this case.
ENABLED Load reconnection is automatic and depends on setpoints Ld recon level and Ld recon
delay. Binary input MAN load recon has no function.
Timer settings
TimerChannel1 … TimerChannel16
Defines the setting of particular timer channel.
There is 16 channels, each defines occurrence date and time (year, month, day, hour, minute), duration time
(in minutes, maximum is 24*60), repeating period (day, week, month, once). In case of week – day of the
week selection, when should be executed + selection of repeating (every 1
st, 2nd, 3rd or 4th week); In case of
month – day of the month selection (e.g. every 3
rd day or every 2nd Monday)
Every channel can be disabled by blocking input (physical input or logical output). If blocking input is active
then the timer is not activated.
All the channels are divided into groups of 4. Every group can have independent binary input. There is also
one common input for all 16 channels.
Act. calls/SMS
History record [ DISABLED / ENABLED ] (FV)
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a History record
type “protection” occurs.
Force value: Yes
Hint:
If enabled for an SMS type active call, an empty Alarmlist would be sent, as this type of protection does not
appear there. So together with the Alarmlist content, the prefix of the History record (“Hst” in english) is sent
to indicate the reason for the active call (available in future SW versions).
Alarm only [ DISABLED / ENABLED ] (FV)
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when an Alarm only
type protection occurs.
Force value: Yes
Warning [ DISABLED / ENABLED ] (FV)
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when a Warning type
protection occurs.
Force value: Yes
Off load [ DISABLED / ENABLED ] (FV)
Enables or disables active calls/SMS/mails to selected phone, mobile or mail address when an Off load type
protection occurs.
Force value: Yes
Hint: