Hint:
To receive active call run InteliMonitor – Type of connection = Active call. Active call window contains list of
received ANT files. Each list item contains Gen-set name, Date, Time, controller serial number.
NumberRings AA [ ]
Number of rings prior to answering the modem connection from PC to controller.
Step: 1
Range: 1 – 30
Hint
:
NumberRings AA change is not accepted immedately but after controller is switched on or when modem is
connected to controller.
ActCallAttempt [ 1 to 250 ]
When an active call is issued, this setpoint defines the number of attempts to deliver the message.
Step: 1
Range: 1 to 250
Hint:
Timeout for connection is 90 sec and after 120 sec controller starts the next attempt. During the time the
controller is trying to issue an active call, incoming calls are blocked.
Date/Time
Time stamp act [ DISABLED / ENGINE RUNNING / ALWAYS ] (FV)
Defines the activity of time stamp function:
DISABLED No periodic records are made.
ENGINE RUNNING Records are made with period given by Time stamp per only if engine is running.
ALWAYS Records are made with period given by Time stamp per regardless of the engine state.
Force value: Yes
Time stamp per
Time interval for periodic history records.
Step: 1 min
Range: 1 - 240 min
#SummerTimeMd [ DISABLED / WINTER / SUMMER,
WINTER-S, SUMMER-S ]
DISABLED: Automatic switching between summer and wintertime is disabled.
WINTER
(SUMMER) : Automatic switching between summer and wintertime is enabled and it is set to
winter (summer) season.
WINTER-S
(SUMMER-S) : Modification for southern hemisphere.
#Time [HHMMSS]
Real time clock adjustment.
#Date [DDMMYYYY]
Actual date adjustment.
Hint
:
#Time and #Date setpoints are synchronized via CAN bus each hour with the lowest address controller.
#Time or #Date change in any controller changes Time or Date in all controllers on CAN bus.