ENABLED mode corresponds to the way that IG and IS controllers (previous generation) handled the
alarms.
Service time 1 [ h ]
Service time 2 [ h ]
Service time 3 [ h ]
Service time 4 [ h ]
Running hours down counters are decremented when engine is running. Service alarm is indicated in Alarm
list and History record is activated when at least one of the counters reaches zero. Service time X setpoints
are actual counter values.
Step: 1 h
Range: 0 – 65535 h
Hint:
Once a service time has elapsed the corresponding Service time X setpoint must be adjusted again to a non-
zero value to clear the alarm and begin a new countdown.
You can rename the particular timers using Translator to indicate specific service intervals – e.g. “OilChange
time”, “SparkPlug time”, ...
Analog protect
The content depends on programmable protections settings. This list contains pre-set protections from
default archives:
Batt >V [ V ]
Warning level for battery over voltage.
Step: 0,1 V
Range: 8,0 – 40,0 V
Batt <V [ V ]
Warning level for low battery voltage.
Step: 0,1 V
Range: 8,0 – 40,0 >V
Batt volt del [ s ]
Delay for battery voltage alarms.
Step: 1 s
Range: 0 – 600,0 s
Gener protect
Hint:
Generator protections are ignored when Process control: ProtectionMode = NOT ACTIVE. This is important
in the case the GCB and engine is not controlled from controller.
The content depends on programmable protections (Universal states) settings. This list contains pre-set
protections from default archives + fixed protections, which are always present.
OverldStrtEval [ % ] (FV)
Specifies the overload level, where the protection evaluation starts (see figure at 2PovrldStEvDel). Under
this level the protection is not active.
Step: 1 % of Nomin power
Range: 100 – 200 %
Force value: Yes