Communication Guide, ©ComAp – March 2014 67
IGS-NT Communication Guide 03-2014.pdf
Active e-mail
Active e-mail can be sent only when operating modem is detected. IG-IB makes five open connection
attempts on active e-mail request. There are three attempts to sent e-mail when connection is opened.
Connection is opened for “Connection holding time” after e-mail is successfully sent.
Note for iG-IB firmware version 1.0 or 1.1 users: active e-mail sending may fail if selected SMTP
server returns a multiline responses. Use firmware version 2.0 to solve this problem.
Configuration items
Internet
Service
Provider
Phone Number
User Name
Password
Data from local Internet provider
Use RTS/CTS
Flow Control
Velocity
Extra Setting
Check if the modem requires RTS/CTS signals.
Only when velocity auto detect is not active.
Those “special” commands for modem configuration are sent to
modem during init procedure.
Connection will be restricted to these terminal IP addresses, i.e.
IG-IB won’t connect to any other address.
Tick “Don’t check” if you want to allow connection to all
terminal IP addresses.
Firmware file name (*.bin) is displayed in this window when old
iG-IB firmware version is detected
Connection to controller
Connection to controller
Two IG-IB’s on CAN bus
Messages window contains messages regarding detected
(actual) firmware version and configuration validity. Here you
can also get information on configuration process.
Get from ISP
Primary DNS
Secondary DNS
SMTP Server
IG-IB mail box
Connection
Holding Time
Keep Permanent
Connection
E-mail setting is necessary only when Active e-mails are
enabled in Controller. It is used as a sender address when iG-IB
sends active e-mail.
After e-mail is successfully sent, waiting for operator response.
If checked connection to ISP is never terminated.
It is established immediately after IG-IB is initialized. If the
communication is interrupted, it is re-established. It is necessary
that the IP address of IG-IB is static so that the PC software
(e.g. WinEdit) “knows” to which address to re-connect.
If this option is not selected, the connection to ISP is
established on request from terminal only. IP address obtained
from ISP is then sent to the terminal via email (IP address can
be dynamic in this case).
Code for unblocking the remote communication with the
controller. Use InteliMonitor/DriveMonitor to enter or change
access code.
Hint:
Some providers have strict requirements for e-mail iG-IB Mailbox address = existing mailbox.