Control Specification SiE12-411
94 Function and Control
3.8 Fan Control
Outline Fan control is carried out according to the following priority.
1. Fan ON control for electric component cooling fan
2. Fan control when defrosting
3. Fan OFF delay when stopped
4. ON/OFF control when cooling operation
5. Fan control when the number of heating rooms decreases
6. Tap control when drooping function is working
7. Fan control when forced operation
8. Fan control in indoor / outdoor silent operation
9. Fan control in the powerful mode
10.Fan control for pressure difference upkeep
Detail Fan OFF Control when Stopped
" Fan OFF delay for 60 seconds must be made when the compressor is stopped.
Fan control when the number of heating room decreases (Only for Heat Pump Model)
When the outdoor air temperature is more than 10°C, the fan must be turned OFF for 30
seconds.
Tap Control in Indoor / Outdoor Unit Silent Operation
1. When Cooling Operation
When the outdoor air temperature is less than 37°C, the fan tap must be set to L.
2. When Heating Operation
When the outdoor air temperature is more than 4°C, the fan tap must be turned to L (only for
heat pump model).
3.9 Moisture Protection Function 2
Outline In order to obtain the dependability of the compressor, the compressor must be stopped
according to the conditions of the temperature of the outdoor air and outdoor heat exchanger.
Detail Heat Pump Model
" Operation stop depending on the outdoor air temperature
Compressor operation turns OFF under the conditions that the system is in cooling operation
and outdoor air temperature is below –10°C.
Cooling Only Model
" Operation stops depending on the outdoor air temperature.
Compressor operation turns OFF under the condition that outdoor air temperature is below
–10°C (10°C for R22 type).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi NX C-Series and is the answer not in the manual?

Daikin Super Multi NX C-Series Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi NX C-Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals