SiE12-411 Troubleshooting
Service Diagnosis 175
5.6 Thermistor or Related Abnormality (Indoor Unit)
Remote
Controller
Display
C4, C9
Method of
Malfunction
Detection
The temperatures detected by the thermistors are used to determine thermistor errors.
Malfunction
Decision
Conditions
When the thermistor input is more than 4.96 V or less than 0.04 V during compressor
operation.
(reference)
When above about 212°C (less than 120 ohms) or below about -50°C (more than 1,860 kohms).
Note: The values vary slightly in some models.
Supposed
Causes
" Faulty connector connection
" Faulty thermistor
" Faulty PCB
Troubleshooting
Check No.6
Refer to P.207
C4 : Heat exchanger temperature thermistor
C9 : Room temperature thermistor
Check the connector connection.
YES
Correct the connection.
Replace the thermistor.
(Replace the indoor unit PCB.)
Replace the indoor unit PCB.
Is it normal?
Is it normal?
(R1403)
NO
Check No. 6
Thermistor resistance check
YES
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin Super Multi NX C-Series and is the answer not in the manual?

Daikin Super Multi NX C-Series Specifications

General IconGeneral
BrandDaikin
ModelSuper Multi NX C-Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals