Outdoor Unit (80 / 90 Class) SiE12-411
238 Removal Procedure
1.10 Removal of Compressor
Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure Points
1
Remove the terminal
cover.
" Be careful to avoid burning
the compressor terminals or
the nameplate.
2
Remove the overload
relay.
3
Disconnect the flag
shape terminal.
As precaution, keep the
contents in memorandum.
4
There is one nut fixing
the compressor.
Remove the nut with a
spanner.
Terminal cover
N
(
brown)
W (blue)
V (yellow)
Terminal nameplate
U (red)
Overload relay
Fixing
plate
Overheat protector