Maintenance
2 sec.
Enter the maintenance menus.
Date - time 1000
It is only necessary to set the correct date and time in connection with the rst use of the
ECL Comfort 110 controller or after a power break of more than 36 hours (see the chapter
on Adapting the ECL Comfort 110 controller).
Flow temp. (ow temperature control) 2000
Heat curve
The ECL Comfort 110 controls the heating system according to the calculated ow
temperature under the inuence of the return and / or room temperature.
The desired ow temperature is dened by 5 settings: ‘Temp. max.’, ‘Temp. min.’, ‘Slope’,
‘Displace’, and ‘Knee point’.
Desired ow temperature
-20 -10 0 10 20-30
20
30
40
50
60
70
80
90
100
110
10
[°C]
[°C]
Heat curve
‘Slope’
‘Temp. max.’
‘Displace’
‘Knee point’
‘Temp. min.’
Outdoor temp.
The calculated ow temperature can be inuenced by connected sensors, ‘Boost’ and ‘Ramp’
etc.