VI.KT.G6.02
22 | © Danfoss | 2016.05
Maintenance
Right digit Dimensioning temperature Capacity
X0 -50 °C large
X1 -45 °C
X5 -25 °C normal
X9 -5 °C small
OFF: No optimization. The heating starts and stops at the times set in the
schedule.
Dimensioning temperature:
The lowest outdoor temperature (usually determined by your system designer in connection
with the design of the heating system) at which the heating system can maintain the
designed room temperature.
Example
The system type is radiator, and the heat accumulation of the building is medium.
The left digit is 2.
The dimensioning temperature is -25 °C, and the capacity is normal.
The right digit is 5.
Result:
The setting is to be changed to 25.
It is only possible make use of ‘Optimize’ if the ECL Comfort 110 controller has a built-in ECA
110 timer program or is connected to an ECA 61.
Based on (optimization based on room / outdoor temp.) 5020
Setting range Factory setting
ROOM / OUT OUT
The optimized start and stop time can be based on either room or outdoor temperature.
ROOM: Optimization based on room temperature, if measured.
OUT: Optimization based on outdoor temperature. Use this setting if the
room temperature is not measured.