VI.KT.G6.02 © Danfoss | 2016.05 | 25
Maintenance
Control param. (control parameters) 6000
Motor prot. (motor protection) 6174
Setting range Factory setting
OFF / 10 ... 59 m OFF
Prevents the controller from unstable temperature control (and resulting actuator oscillations). This
can occur at very low load. The motor protection increases the lifetime of all involved components.
OFF: Motor protection is not activated.
10 ... 59: Motor protection is activated after the set activation delay.
Typically used for DHW applications. Can also be used for heating systems at very low load.
Xp (proportional band) 6184
Setting range Factory setting
1 ... 250 K 80 K
Set the proportional band. A higher value will result in a stable but slow control of the
ow temperature.
Tn (integration time constant) 6185
Setting range Factory setting
5 ... 999 s 30 s
Set a high integration time constant to obtain a slow but stable reaction to deviations.
A low integration constant will make the controller react fast but with less stability.
M1 run (running time of the motorized control valve) 6186
Setting range Factory setting
5 ... 250 s 35 s
‘M1 run’ is the time it takes the controlled unit to move from fully closed to fully open
position. Set the ‘M1 run’ according to the example.