VI.KT.G6.02 © Danfoss | 2016.05 | 21
Maintenance
Ramp (reference ramping) 5013
Setting range Factory setting
OFF / 1 ... 99 m OFF
The time in which the desired ow temperature increases gradually to avoid load peaks in the heat
supply.
Set the ramping time for the controller.
Temp. °C
Time (min.)
Setting line 5013
In order to avoid load peaks in the supply network, the ow temperature can be set to
increase gradually after a period with setback temperature. This causes the valve to open
gradually.
Optimizer (optimizing time constant) 5014
Setting range Factory setting
OFF / 10 ... 59 OFF
Optimizes the start and stop times for the comfort temperature period to obtain the best comfort at the
lowest energy consumption. The lower the outdoor temperature, the earlier the heating cut-in.
Adjust the optimizing time constant.
The value consists of a two digit number. The two digits have the following meaning:
Left digit Heat accumulation of the building System type
1X light
Radiator systems2X medium
3X heavy
4X medium
Floor heating systems
5X heavy

Table of Contents

Other manuals for Danfoss ECL Comfort 110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort 110 and is the answer not in the manual?

Danfoss ECL Comfort 110 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort 110
CategoryController
LanguageEnglish

Related product manuals