Maintenance
ECA address (choice of room panel / remote control) 7010
Setting range Factory setting
OFF / A / B OFF
Decides the communication with the room panel or remote control.
OFF: Room temperature sensor (no room panel / remote control)
A: Remote control, ECA 61 with address A
B: Remote control, ECA 61 with address B
P1 exercise (pump exercise) 7022
Setting range Factory setting
ON / OFF ON
Exercises the pump to avoid blocking in periods without heat demand.
ON: The pump is switched ON for 1 minute every third day around noon.
OFF: The pump exercise is not active.
M1 exercise (valve exercise) 7023
Setting range Factory setting
ON / OFF OFF
Exercises the valve to avoid blocking in periods without heat demand.
ON: The valve receives a signal to open and close every third day around
noon.
OFF: The valve exercise is not active.
Actuator (gear motor / thermo actuator) 7024
Setting range Factory setting
GEAR / ABV GEAR
Choose the actuator type for your valve.
GEAR: Gear motor
ABV: Thermo actuator (Danfoss type ABV)
Control parameters (lines 6174-6187) are overruled if thermo actuator is chosen (ABV).
Application 7000