Maintenance
This limitation is based on a PI regulation where P (Gain) responds quickly to deviations
and I (Intgr. time) responds slower and over time removes the small osets between the
desired and actual values. This is done by changing the desired ow temperature.
Intgr. time (time constant for room temp.) 3015
Setting range Factory setting
OFF / 1 ... 50 OFF
Controls how fast the room temperature adapts to the desired room temperature (I control).
OFF: The control function is not inuenced by the ‘Intgr. time’.
1: The desired temperature is adapted quickly.
50: The desired temperature is adapted slowly.
Gain - max. (room temp. limitation, max.) 3182
Setting range Factory setting
-9.9 ... 0.0 -4.0
Determines how much the ow temperature will be inuenced (decreased) if the room temperature is
higher than the desired room temperature (P control).
-9.9: The room temperature has a big inuence.
0.0: The room temperature has no inuence.
Gain - min. (room temp. limitation, min.) 3183
Setting range Factory setting
0.0 ... 9.9 0.0
Determines how much the ow temperature will be inuenced (increased) if the room temperature is
lower than the desired room temperature (P control).
0.0: The room temperature has no inuence.
9.9: The room temperature has a big inuence.