VI.KT.G6.02 © Danfoss | 2016.05 | 23
Maintenance
Total stop 5021
Setting range Factory setting
ON / OFF OFF
Decide whether you want a total stop during the setback temperature period.
ON: The desired system temperature is lowered to ‘Standby T’ (line 7093).
Temp. min.’ (line 2177) is overruled.
Desired system temp. °C
Standby T
Time
OFF: No total stop
Desired system temp. °C
Standby T
Time
S1 T lter (outdoor temp. lter) 5081
Setting range Factory setting
1 ... 200 100
Dampens the measured outdoor temperatures by the set factor.
1: Fast (low lter constant)
200: Slow (high lter constant)