Maintenance
P1 heat T (heat demand) 7078
Setting range Factory setting
5 ... 40 °C 20 °C
When the desired ow temperature is above the set temperature in ‘P1 heat T’, the controller
automatically switches ON the circulation pump to meet the heat demand.
5 ... 40: The circulation pump is ON above the set value.
The valve is fully closed as long as the pump is not switched on.
Standby T (standby temperature) 7093
Setting range Factory setting
5 ... 40 °C 10 °C
Set the desired ow temperature at standby (e.g. during total stop).
5 ... 40: Desired standby ow temperature.
Ext. (external override) 7141
Setting range Factory setting
OFF / SETBACK / COMFORT OFF
Choose mode for ‘Ext.’ (external override).
The override can be activated for setback or comfort mode. For override, the controller
mode must be AUTO (scheduled operation).
OFF: The controller's schedule is not overridden.
SETBACK: The controller is in setback mode when terminals 11 and 12
are short-circuited.
COMFORT: The controller is in comfort mode when terminals 11 and 12
are short-circuited.

Table of Contents

Other manuals for Danfoss ECL Comfort 110

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss ECL Comfort 110 and is the answer not in the manual?

Danfoss ECL Comfort 110 Specifications

General IconGeneral
BrandDanfoss
ModelECL Comfort 110
CategoryController
LanguageEnglish

Related product manuals